Road Tunnels Manual

You are here

fire Resistance of structures

The fire resistance of a structure can be characterised by the time which elapses between the start of a fire and the time when the structure does not ensure its function any longer, due to unacceptable deformation or collapse.

Chapter 7 "Design Criteria for Structure Resistance to Fire" of technical report 2007 05.16.B "Systems and Equipment for Fire and Smoke Control in Road Tunnels" summarises the objectives of structural fire resistance in tunnels as follows:

  1. people inside the tunnel shall be able to self-evacuate (self-rescue) or be assisted to a safe place (main objective)
  2. rescue operations shall be possible under safe conditions
  3. protective measures shall be taken against collapse of tunnel structure and loss of property to third parties

A supplementary objective is to limit the time during which traffic will be disrupted due to the repairs after a fire.

An overview of the subject was published in Chapter VII.4 "Fire resistance of structures" of technical report 1999 05.05.B "Fire and Smoke Control in Tunnels".

The fire resistance of structures is described in relation to different time-temperature curves. Figure 1 shows the ISO 834 curve, the Dutch RWS curve, German ZTV curve and a French 'increased' Hydrocarbon curve, HCinc, in which the temperatures are multiplied by a factor of 1300/1100 from the basic Hydrocarbon (HC) curve of Eurocode 1 Part 2-2.

Figure 1: Temperature versus time curves for ISO, HCinc, ZTV and RWS standards (Routes/Roads No. 324)

Design criteria for resistance to fire in tunnels have been agreed between the World Road Association (PIARC) and the International Tunnelling Association, as presented in the Routes/Roads article "PIARC Design Criteria for Resistance to Fire for Road Tunnel Structures" (2004), and published as a PIARC recommendation in Chapter 7 "Design Criteria for Structure Resistance to Fire" of technical report 2007 05.16.B.

A summary of the proposals is presented in Table 1. On the basis of the time-temperature curves presented in figure 1 above, table 1 identifies the curve to be chosen and the duration during which this curve must be respected. This information is given for different types of main structures and secondary structures and for two types of traffic: cars/vans and lorries/tankers.

Table 1: PIARC and ITA recommendations

Traffic Type

Main Structure

Secondary Structures (4)

- Immersed or
Under/Inside
Superstructure
Tunnel in Unstable Ground Tunnel in Stable Ground Cut & Cover Air Ducts (5) Emergency Exits
to Open Air
Emergency Exits to
Other Tube
Shelters (6)
Cars
Vans
ISO
60 min
ISO
60 min
See note (2) See note (2) ISO
60 min
ISO
30 min
ISO
60 min
ISO
60 min
Lorries
Tankers
RWS/HCinc
120 min (1)
RWS/HCinc
120 min (1)
See note (3) See note (3) ISO
120 min
ISO
30 min
RWS/HCinc
120 min
RWS/HCinc
120 min (7)

Notes

(1) 180 min may be required for very heavy traffic density of lorries carrying combustible goods.

(2) Safety is not a criterion and does not require any fire resistance (other than avoiding progressive collapse). Taking into account other objectives may lead to the following requirements:

  • ISO 60 min in most cases;
  • no protection at all if structural protection would be too expensive compared to cost and inconvenience of repair works after a fire (e.g. light cover for noise protection).

(3) Safety is not a criterion and does not require any fire resistance (other than avoiding progressive collapse). Taking into account other objectives may lead to the following requirements:

  • RWS/HCinc 120 min if strong protection is required because of property (e.g. tunnel under a building) or large influence on road network;
  • ISO 120 min in most cases, when this provides a reasonably inexpensive way to limit property damage;
  • no protection at all if structural protection would be too expensive compared to cost and inconvenience of repair works after a fire (e.g. light cover for noise protection).

(4) Other secondary structures: should be defined on a project-specific basis.

(5) In case of transverse ventilation.

(6) Shelters should be connected to the open air.

(7) A longer time may be considered if there is a very heavy volume of lorries carrying combustible goods and evacuation from the shelters is not possible within 120 min.

The consequences of failure will influence the requirements for fire resistance. This depends on the type of tunnel. In an immersed tunnel, for example, a local collapse can cause the whole tunnel to be flooded whereas local collapse in a cut-and-cover tunnel may have very limited consequences. A basic requirement is that progressive collapse must be prevented and vital longitudinal systems, such as an electrical supply or communication cables, are not cut off.

The materials used in tunnel structures involve different precautions for fire protection. Section VII.3 "Fire reaction of materials" of the report 1999 05.05.B "Fire and Smoke Control in Tunnels" discusses the characteristics of rock tunnel linings versus reinforced concrete. The intensity of the heat generated during a major fire may cause reinforced concrete to lose its supporting function. The role of insulation using fire-resistant protection can be applied to prevent early damage to the structure. The fire resistance of the total construction (type and depth of reinforcement/prestressing, additional protection, etc.) needs to be considered.

Figure 3: Damaged structure of the Gothard tunnel following the fire in 2001Spalling of concrete is caused by differences in temperature and expansion. It causes a danger for the reinforcement which is more easily exposed to high temperatures. It will generally not be a danger for evacuating people, but it may be dangerous for firemen. Various types of fire-resistant protection can be used to reduce the risk and the effects of spalling, although it can never be completely prevented due to the high temperatures that may occur.

Attention must be given to the fire resistance of the ventilation system so that its design performance is not impaired by failure. Therefore it is necessary to examine the consequences of a local collapse of a duct in case of fire.

Escape routes are only used during the first phase of the fire for the escape of trapped people. It must be possible to use such routes for a period of at least 30 minutes. In cases where these routes are also used by the rescue and fire teams, the period may be longer.

To avoid fire spreading into an adjacent tube or escape route, emergency doors, emergency recesses and other equipment located between two traffic tubes, should remain intact during a specified period of time. The whole emergency door and surrounding construction, including the door frame, should resist fire for at least a 30 minute fire exposure. For a door between two traffic tubes, a much longer resistance is required, for example 1 to 2 hours.       

Reference sources

No reference sources found.